  • How does lead-lag sequencing work in an Evomax 2 cascade?

    The Evomax 2 Cascade includes a built-in cascade control option that manages lead-lag sequencing automatically, rotating which boiler fires first so run hours are balanced across the cascade rather than one unit taking all the wear. For larger installations this can typically also be linked into a building management system, giving facilities teams centralised monitoring alongside the boiler's own sequencing logic.

  • Does Evomax 2 cascade control work with variable primary flow?

    Variable primary flow, where pump speed responds directly to system demand rather than running at a fixed rate, is a common commercial plant room strategy, and cascade-controlled boilers like the Evomax 2 need their sequencing logic and the pump control strategy designed together so boilers aren't staged on or off out of step with actual flow. Getting this coordination right at design stage avoids inefficient cycling once the system is commissioned.

  • What's the benefit of an N+1 cascade of wall hung boilers?

    An N+1 Evomax 2 cascade includes one additional boiler beyond the number needed to meet the calculated heating load, providing redundancy across several smaller wall-hung units. For example, if five boilers are required to meet the full load, a six-boiler cascade allows one to be taken out of service while the remaining five continue to heat the building. By comparison, a duty-and-standby arrangement requires each boiler to be capable of meeting the full heating load independently.

  • What is the best commercial boiler in the UK?

    Evomax 2 is the UK’s number one wall-mounted commercial boiler. The range is available in outputs from 30kW to 150kW and up to 6 boilers can be cascaded for outputs up to 900kW.

    An Evomax 2 three-boiler cascade can be built in less than 90 minutes when using our prefabricated frame and header kits - watch our video now! How quickly can you build a three-boiler cascade?

  • Do you offer free commissioning on the Evomax 2?

    Yes, Ideal Heating offers free commissioning on its commercial products. This needs to take place within three months of installation to qualify for full warranty.

    The free commissioning service is available on the following products: Evomax 2, Imax Xtra 2, Imax Xtra EL, Evomod commercial boilers, the EQMAX water heaters and ECOMOD commercial heat pumps.

    To take advantage of their market-leading free commissioning service, simply fill in a few details: Free Commissioning Request

  • Do wall hung boilers fitted in cascade improve part-load efficiency?

    Yes, this is one of the main engineering arguments for a cascade. A single large boiler often sits well below its rated output for most of the year and can short-cycle at low loads, while a cascade of smaller Evomax 2 units matches output to demand by staging boilers on and off individually, so each running unit operates closer to its efficient firing range.

  • How many Evomax 2 boilers can you cascade?

    You can cascade up to 6 Evomax 2 boilers for outputs up to 900kW.

    Evomax 2 wall-mounted commercial boiler is available in outputs 30kW – 150kW. Find out more about the Evomax 2 the UK’s number one wall-mounted commercial boiler at: Evomax 2 Cascade and PHEX

  • What flue arrangements are required for a wall hung boiler cascade system?

    Flue design becomes a bigger part of the plant room layout as cascade size increases, since each wall hung boiler in the Evomax 2 cascade system typically needs its own flue run or a shared terminal arrangement designed to manage the combined plume. This is very site-specific, so our specification team usually reviews flue routing alongside the cascade configuration rather than treating them as separate decisions.